S105

OMA0603

1504,00  VAT 0%

In stock (can be backordered)

The Ouman S105 is a compact and versatile air conditioning controller controller designed to manage 1-5 stage air conditioners: dampers, cooling, heat recovery, heating and fan controls. It is suitable for both stepless frequency converter-controlled and fixed-speed contactor-controlled AH devices, including AH devices with a battery.

Ouman S105 is an intelligent air handling unit controller that is suitable for all kinds of applications. The controller s diverse and innovative control solutions are as easy to use as the other Ouman controllers that have a reputation for user friendliness. The controller makes it possible to maintain optimal air handling in spite of changing conditions in the room to be ventilated (temperature, CO2 content, humidity, air volume, channel pressure).

Optimal ventilation enhances comfort, safeguards structures and the ventilation device itself, while also conserving energy. Poor air quality leads to fatigue and reduces productivity, while excessively humid air compromises structures. Whether it be in a classroom, auditorium, banquet hall, or workspace, there will always be fresh and highquality air.

Brochure

ENG

User manual

ENG SWE EST

Dimensions:
width 230 mm, height 160 mm, depth 60 mm
Weight:
1.3 kg
Protection class:
IP 41
Operating temperature:
0 ºC … +50 ºC
Storing temperature:
-20 ºC … +70 ºC
Power supply L(91), N (92):
– Operating voltage/ Power requirement: In addition, use an external 24VAC power supply if the combined operating voltage of triac and 24VAC outputs exceeds 23VA.
– Maximum load for internal 24 VAC power supply: 1A/23 VA
– Front fuse: max 10A
Measurement inputs:
– Sensor measurement(inputs 1-16, connectors 11-26):
Measurement channel accuracy: Also sensor tolerances and the effect of cables must be considered when calculating total accuracy.
– NTC10: ±0.1 ºC between -50 ºC … +100 ºC and ±0.25 ºC between 100 ºC … 130 ºC
– NTC20: ±0.1 ºC between -20 ºC … 130 ºC and ±0.5 ºC between -50 ºC … -20 ºC
– NTC1.8: ±0.1 ºC between -50 ºC … +100°C and ±0.4 ºC between 100 ºC … +130 ºC
– NTC2.2: ±0.1 ºC between -50 ºC … +100 °C and ±0.6 ºC between 100 ºC … +130 ºC
– Ni1000LG: ±0,2 ºC between -50 ºC … +130 ºC
– Ni1000DIN: ±0,2 ºCbetween -50 ºC … +130 ºC
– Pt1000: ±0,2 ºC between -50 ºC … +130 ºC
– Milliampere signal (inputs 1-16, connectors 11-26):
Inputs 12-15 (terminals 22-25) directly support current measurement. If current measurement is connected to inputs 1 – 11 and 16 (terminals 11 – 21 and 26), a 500 Ω parallel resistor must be connected to the measurement channel.
0/4 – 20 mA current signal, measurement accuracy 0.1 mA.
Note! If the measurement range of the transmitter measurement is different from 0 – 20 mA, change the Minimum /Maximum setting values of that input (Input configuration -> UIx -> Advanced settings)
– Voltage measurement (inputs 1-16, connectors 11-26):
0 (2) -10V voltage message, meas. accuracy 50 mV.
Note! If the measurement range of the transmitter measurement is different from 0 – 10V, change the Minimum /Maximum setting values of that input (Input configuration -> UIx -> Advanced settings)
– Digital inputs (inputs 1-16 and DI1 – DI2, connectors 11-28):
Contact voltage 15 Vdc (inputs 27 and 28), Contact voltage 5 Vdc (inputs 25 and 26). Switching current 1.5 mA (inputs 27 and 28), switching current 0.5 mA (inputs 25 and 26). Transfer resistance max. 500 Ω (closed), min. 11 k Ω (open). Inputs 27 and 28 are pulse inputs and input 26 is used for status information.
Analog outputs (53,54,64,66,68,70): Output voltage range 0…10 V. Output current max 7 mA /output
15V voltage output (1): 15 VDC output maximum load 100 mA
24 VAC voltage outputs (51, 52): Output current max. 1A / output
Without external power supply the total continuous load capacity of triac outputs and 24 Vac outputs is 23 VA
Control outputs Triac (55…60): 24 Vac. Triac-outputs are in pairs (55, 56), (57, 58) and (59, 60).
The total current output of each pair is max. 1A. Without external power supply the total continuous load capacity of triac outputs and 24 Vac outputs is 23VA
Data transfer connections:
– RS-485-bus (3 and 6) (A and B): Galvanically isolated, supported protocols Modbus-RTU
– MicroSD memory card: Memory card is not included in the delivery. Technical requirements to microSD memory card: Standard micro SDHC, UHS, Capacity 512 MB…32 GB, File system FAT 32, Class: 4…10+
Warranty: 2 years
APPROVALS
– EMC-directive: 2014/30/EU
– Interference tolerance: EN 61000-6-1
– Interference emissions: EN 61000-6-3