Ouman H23 is suitable for every house with central water heating. H23 is open to different types of remote monitoring solutions. House heating can now be monitored and controlled from the display of a GSM-phone, PC, and from the controller. Alarm messages can be received as text messages into a GSM-phone. H23 can be connected to Ounet-service via Oulink-ETH adapter (TCP/IP, optional) or other monitoring systems using a Modbus RTU.

• Operating voltage: 230 VAC, 50 Hz
• The internal 24 V power source, total load capacity of max. 1A/23VA
• Dimensions W230 x H160 x D60
• Three switches on the cover for circulation pumps

Brochure

ENG

User manual

ENG

Dimensions: width 230 mm, height 160 mm, depth 60 mm
Weight: 1.3 kg
Protection class: IP 41
Operating temperature: 0 ºC…+50 ºC
Storing temperature: -20 ºC…+70 ºC
Power supply: L (91), N (92-94)
– Operating voltage 230 Vac / 200 mA
– The internal 24 V power source, total load capacity of max. 1 A/23 VA
– Front fuse max 10A
Measurements inputs:
– Sensor measurements (11-19) Measurement channel accuracy:
– NTC10-element: ±0,15 ºC between -50 ºC…+100 ºC
Also sensor tolerances and the effect of cables must be considered when calculating total accuracy. Measurement M1 can be connected also from outside of the casing by a plug-connector.
– Digital inputs (27, 28): Contact voltage 15 Vdc, switching current 5 mA. Transfer resistance max. 250 Ω (closed), min. 350 Ω (open).
Analog outputs (66, 68, 70): Output voltage range 0…10 V. Output current max. 10 mA / output
15 VDC output (1): 15 VDC output maximum load 100 mA
24 VAC output (51): Total current of 24 VAC output and triac-outputs max. 1A.
Pump control contacts (81-89): Contacts for three circulation pump. Pumps are controlled by a switches on the top of the H23 device. Relay max. load 3A.
Protective earth terminal (73-78): Protective earth terminal block for 230V devices. Control circuit fuse max. 10A
Control outputs (51): 24 VAC -control output
– Triac (55…60): Total current of triac-outputs and 24 VAC output max. 1A.
Data transfer connections
– RS-485-bus A (3) and B (6): Unisolated, supported protocols Modbus-RTU
Options
– OULINK-ETH OULINK ETH adapter provides Modbus TCP / IP interface for H23 device.
– GSMMOD: By connecting the GSM modem to the H23 , you can communicate with the text messages to device and receive alarms to GSM phone.

APPROVALS
– EMC-directive: 2004/108/EC, 93/68/EEC
– Interference tolerance: EN 61000-6-1
– Interference emissions: EN 61000-6-3