Ouman C203 is a DIN-rail mounted heating controller. Its versatility, intelligence and openness make it an ideal heating controller for all water circulation heating systems. Ouman C203 is really easy to use – informative display panel and GSM Control – feature enable reliable use anytime, anywhere! C203 can be connected to Ounet-service via M-LINK-adapter (TCP/IP, optional) or other monitoring systems using a Modbus RTU.

Mounting

Protection class

Operating voltage

Data transferring connectors

Approvals

,

Applications

Hakunimi

Brochure

ENG SWE EST LIT RUS

User manual

ENG SWE EST LAV LIT POL RUS

Deployment manual

ENG SWE EST LAV LIT POL RUS

Protection class: IP 20
Operating temperature:
0 ºC…+40 ºC
0 ºC…+50 ºC under the following conditions:
– 24 Vac outputs the maximum load: a total of 300 mA
– 15 Vdc output maximum load: 100 mA
– The relay and triac outputs, maximum load:
230V/450 mA individual relay and triac outputs per
Storing temperature: -20 ºC…+70ºC
Power supply
– Operating voltage: 230 Vac / 125 mA
The internal 24 V power source, total load capacity of max. 0.4 A/10 VA continuously, temporary (60 s) 15 VA
– Backup input: 12 Vdc
Measurement inputs:

  • Sensor measurements (inputs 1…13) Measurement channel accuracy:
  • Also sensor tolerances and the effect of cables must be considered when calculating total accuracy.
    – NTC10: +0.1 ºC between -50 ºC…+100 ºC and +0.25 ºC between 100 ºC…130 ºC
    – NTC20: +0.1 ºC between -20 ºC…130 ºC and 0.5 ºC between -50 ºC…-20 ºC
    – NTC1.8: +0.1 ºC between -50 ºC…+100°C and -0.4 ºC between 100 ºC…+130 ºC
    – NTC2.2: +0.1 ºC between -50 ºC…+100 °C and -0.6 ºC between 100 ºC…+130 ºC
    -Ni1000LG: +0,2 ºC between -50 ºC…+130 ºC
    -Ni1000DIN: +0,2 ºCbetween -50 ºC…+130 ºC
    -Pt1000: +0,2 ºC between -50 ºC…+130 ºC

  • Milliampere signal (inputs 12-14) 0 – 20 mA current message, meas. accuracy 0.1 mA
  • Voltage measurement (inputs 4, 7, 12-14) 0…10 V voltage message, meas. accuracy 50 mV
  • Digital inputs (inputs 12-17) Contact voltage 15 Vdc (input 17), contact voltage 5 Vdc (input 12-16). Switching current 1.5 mA (input 17), switching current 0.5 mA (input 12-16). Transfer resistance max. 500 Ω (closed), min. 11 k Ω (open).
  • Counter inputs (17 and 18) Minimum pulse length 30 ms
  • Analog outputs
    (27, 30, 43, 46, 49, 50): Output voltage range 0…10 V. Output current max 10 mA /output
    24 VAC voltage outputs
    (28, 41, 44, 47): Output current max 1 A /output. Without external power supply outputs current max. a total of 10 VA continuously, temporary (60 s) 15 VA.
    Relay outputs
    – Change-over contact relay (71…76): 2 pcs, 230 V, 1 A
    Triac outputs
    – 230 Vac (77…80): 2 pcs, 230 V, max 1 A / output. Potential-free AC switch. DC controls require intermediate relay.
    – 24 Vac (24, 25): 24 Vac. Output current max. a total of 1 A. Without external power supply outputs current max. a total of 10 VA continuously, temporary (60 s) 15 VA.
    Data transfer connections
    – RS-485 bus (A1 and B1): Galvanically isolated, supported protocols Modbus-RTU
    Option
    – M-LINK: M-LINK adapter provides Modbus TCP / IP interface for C203 device.
    – GSMMOD: By connecting the modem to the C203 controller, you can communicate with the regulator text messages and pass this information on alarms to your mobile via SMS. The modem is connected to either the device or the M-LINK adapter RJ-45 connector. GSMMOD is powered by the C203 (terminal 52 and 53).
    APPROVALS:
    – EMC-directive: 2004/108/EC, 93/68/EEC
    – Interference tolerance: EN 61000-6-1
    – Interference emissions: EN 61000-6-3