DPT/D

OMB0035

243,00  VAT 0%

In stock

Differential pressure transmitter with display. The DPT is an electronic differential pressure transmitter used for measuring low pressures of air and non-aggressive gasses in order to monitor and control pressures in building automation, HVAC and clean room systems. Measuring range can be selected from -100 Pa and 2500 Pa between. Transmitter has an automatic reset.

Dimensions 7,15 × 9 × 3,6 cm
Operating voltage

,

Measuring element

Protection class

Approvals

Data sheet

FIN-ENG-SWE-RUS

Dimensions: 90,0 x 71,5 x 36,0 mm
Weight: 150 grams, with accessories 290 grams
Materials
– Housing: ABS
– Cover: PC
– Pressure connections: ABS
– Duct connectors: ABS
– Tubing: PVC, soft
Accuracy (measured pressure): +1.5% or (+ 3 Pa >250 Pa).(including: general accuracy, temperature drift, linearity, hysteresis and repetition error)
Response time: 0.8 / 4 s selectable by jumper
Bursting pressure: 400 kPa
Suitable media: Air and non-aggressive gases
Measuring element: Piezoresistive
Electrical interface (3-wire):
– Supply voltage: 24 VAC or VDC
– Max. tolerance: +/- 10%
– Power consumption: < 1.0 W (<1.5W with Iout 20mA) - Output signal: 0…10 VDC, Load R minimum 1kΩ or 4…20 mA, maximum load 500 Ω Electrical connections: 4 screw terminals, max 1.5 mm2 Cable entry: M16 Pressure connections: Male Ø 5,0 mm and 6,3 mm Operation temperature: -10…+50°C Storage temperature: -20…+70°C Ambient humidity: 0 to 95% RHw Safety: - Protection standard: IP54 - Conformance: Meets the requirements for CE marking - EMC directive: 2004/108/EY - Rohs directive: 2002/95/EY