Product videos

OUFLEX A

OMA0518

1978,00  VAT 0%

Note! Ouflex programming training is required to purchase this product

 

The Ouman Ouflex A presents an advanced automation system designed to efficiently monitor and manage building automation within a property. Programming the Ouflex A building automation system is seamlessly achieved using the user-friendly Ouflex Tool. A crucial component of the Ouman property automation system, the Ounet web-based SCADA, seamlessly integrates with the Ouflex A.

Mounted on a DIN-track, the Ouflex A is a versatile device for monitoring, controlling, and adjusting various parameters. With 34 I/O points and a range of telecom and bus connections, it offers flexible connectivity options. Moreover, it provides 24 V AC and 15 V DC voltage outputs. The device is equipped with a built-in Web UI accessible via LAN or the internet, enabling remote control capabilities anytime, anywhere. The display module of the device can be detached and relocated for convenience.

Expanding the number of I/O points is made possible through external I/O modules connected via bus connections. Designed to comply with DIN standards, the device can be mounted on most substation cabinet models, aided by detachable terminal blocks that simplify the installation process.

Brochure

ENG SWE EST

User manual

ENG SWE EST

Dimensions: width 213,5 mm, height 93,3 mm, depth 96,8 mm
Weight: 0.7 kg
Protection class: IP 20
Operating temperature: 0 ºC…+40 ºC
Storing temperature: -20 ºC…+70 ºC
Power supply
– Operating voltage: 24 Vac, 50 Hz (22 Vac – 33 Vac)
– Power required: (15 Vdc output =if not connected) 13 VA, (15 Vdc output = 750 mA) 34 VA, Notice! Please consider 24 Vac operating voltage and power required for Triac outputs.
– Backup input: 12 Vdc
– Current consumption: 300mA / 3,6W (relays not in use), 400mA / 4,8W (relays in use)
Universal measurement input (can be configured) measurement types:
Passive sensors (inputs 1…16) Measurement channel accuracy:
• NTC10: +0,1 ºC between -50 ºC…+100 ºC , +0,25 ºC between +100 ºC…+130 ºC
• NTC 1.8 +0,2 ºC between -20 ºC…+40 ºC, +0,6 ºC between +40°C…+70 ºC and +2.0 temp.
over 75°C.
• NTC 2.2: +0,2 ºC between -20 ºC…+55 ºC, +0,5 ºC between +60°C…+70 ºC and +2.0 temp.
over 75°C.
• NTC 20: +0,1 ºC between -20 ºC…+70 ºC, +0,6 ºC between +75ºC…+120° C
• Ni1000: +1,0 ºC between -50 ºC…+130 ºC
• Ni1000DIN: +0,2 ºC between 100 ºC…+130 ºC, +0,5 ºC between -5 ºC…-20 ºC
• PT1000 element: +1,0 ºC between -50 ºC…+130 ºC
Also sensor tolerances and the effect of cables must be considered when calculating total
accuracy.

Active sensors (inputs 1…16): 0…10 V voltage message, meas. accuracy 1 mV. Milliampere signal with shunt resistor 0/4-20 mA
Contact information (inputs 1…16): Contact voltage 5 Vdc. Contact current 0,5 mA. Contact resistance max 1,9 kΩ (closed), min 11 kΩ (open)
Counter inputs (inputs 13…16): Minimum pulse length 30 ms
Digital input measurement types:
– Contact information (inputs 21 and 22): Contact voltage 15 Vdc. Contact current 1,5 mA. Contact resistance max 500 Ω (closed), min 1,6 kΩ (open)
– Counter inputs (inputs 21…22): Minimum pulse length 30 ms
Analog outputs (61…66): Output voltage range 0…10 V. Output current max 10 mA/output.
Relay output
– Change-over contact relay (71…76): 2 pcs, 230 V, 6 A
– Normally open contact relay (77…84): 4 pcs, 230 V, 6 A
Triac outputs
24 Vac (42 and 43): Output current together max 1 A
24 Vac (44 and 45): Output current together max 1 A
Operating voltage outputs
– 5 pcs 24 Vac outputs (41): Output current max 1 A /output
– 15 Vdc output: Output current max 750 mA
Data transfer connections
– RS-485 bus (A1 and B1): Galvanically isolated, supported protocols Modbus-RTU
– RS-485 bus (A2 and B2): Galvanically isolated, supported protocols Modbus-RTU
– USB-host connection: RS-232-modem, Ouman GSM modem
– USB-device connection: Yes
– Ethernet: Full-duplex 10/100 Mbit/s, supported protocols Modbus-TCP/IP
– Ouman Access: Intelligent remote connection built-in for use with Ounet and Ouflex Tool